IEC 61850 demonstrator · protection and automation

Fault simulator · VIRTUS 225/110 kV substation

IEC 61850 · simulated in your browser --:--:--

225 kV line VIRTUS – ROUVIÈRES · 80 km Move the lightning bolt along the line, click to strike

Settings

Faults run on an IEC 61850 test bench: sampled values out, GOOSE back. Tripping times are measured, not scripted.

Bench not reached: the relay is simulated in your browser.

Line

Bay
L61ROUVI · ROUVIÈRES
Voltage
225 kV · 50 Hz
Length
80 km · 212 towers
Impedance
0.06 + j0.40 Ω/km
Protection
Distance · Z1 80 % instant · Z2 120 % at 0.5 s · acceleration · weak-infeed echo
Breaker
60 ms break time
Reclosing
Single-pole · three-pole after single-pole · delayed three-pole with synchro-check

Fault

5 Ω

A fault is permanent only if the short circuit is still there after the last reclosure.

Auto-recloser

2.0 s 5 s 5 s 90 s

From 2.5 s single-pole dead time, pole discordance trips all three poles.

Automation and testing

180 s

Plan value 180 s: shorten it to watch the sequence. In test mode no breaker moves.

Setting plan, 225 kV line feeder

TCMRMSingle-pole dead time2 s
TCTRTThree-pole dead time5 s
TRVLRT · TRVBRTDead-line · dead-bus closing2 s · 2 s
TICRTCriteria changeover5 s
TDRTThree-pole cycle disarm90 s
TB1 · TB2Blocking after a closing: fast · slow protection3 s · 30 s
TRBreaker recovery after a closing60 s
PTL/PTB · ATL/ATBVoltage present · absent80 % · 30 % Un
ΔU · Δφ · TGSynchro-check, slip20 % · 30° · 3 s
TARDMU · TDMUUndervoltage: arming, tripping1 s · 180 s
T2 · T3 · T4Distance protection, zones 2 to 40.5 · 1.6 · 2.4 s

Typical settings of a 225 kV line feeder.

Reading the event recorder

DEB / FIN
start and end of a signal
FUG
transient signal: trip, order, refusal
OUV / FER
operation ordered by the operator or the control center
DEC / ENC
opening or closing by protection or automation
O?F
breaker poles in different positions (single-pole open)
ES / HS
function in service, out of service
AUTO
protection or automation
OPE
operator, here this web page
CDT
remote control (control center)
INV / TST
invalid quality, test data

French labels, as in substation control rooms. Hover a line for its IEC 61850 object.

SCADA · VIRTUS substation A1 0/0 A2 0/0 No alarm

Event recorder VIRTUS · operating log, in French as in the substation